1. Application |
|
DZ30 miniature circuit breaker is used in the single phase residual current of AC50/60Hz, rated voltage 220V or below for protecting electron circuit from overload and short circuitl This product has advantages of high breaking capacity, small volume, width is only 18mm. Zero and live wire are cut off at the same time, preventing the person and fire danger. It is the idealest distribution protective switch in the civil residence field at present. This product conforms to the requiremetn of IEC60898.
|
|
2. Type and meanings |
|
|
2. Main technical parameter |
|
Rated current(A) |
No.of pole |
Rated voltage(V) |
Rated curret of frame |
Rated capacity of short circuit |
Mechanical life |
6,10,16,20,25,32 |
1+N |
230 |
3000 |
0.65~0.70 |
20000 |
|
|
3. Overload current tripping characteristic |
|
Testing current |
Rated current |
Limited time |
Appointed resalt |
Start state |
Note |
1.13In |
all |
t=1h |
non-trip |
cold state |
|
1.45In |
all |
t<1h |
trip |
heat state |
The current risn steadily to a fixed
value within 5s |
2.55In |
all |
1 <60S< div> |
trip |
cold state |
|
5In |
all |
t=0.1s |
non-trip |
cold state |
Open the supplementary switch,
connect the power |
10In |
all |
t<0.1s |
trip |
cold state |
Open the supplementary switch,
connect the power |
|
|
4. Motion characteristic curve
|
|
|
5. Outline and installation dimensions |
|
|
|